Description: SITC of Power room Panel for the proposed NMS equipment at 2nd floor DTAX Exchange Trichy Name of Work SITC of Power room Panel for the proposed NMS equipment at 2nd floor DTAX Exchange Trichy
Details: SITC of floor mounting cubicle type LT panel suitable for 415V, 3 phase, 4 wire, 50 Hz AC supply system fabricated in compartmentalized design from CRCA sheet of 2 mm thick for frame work & load bearing members and 1.6 mm for covers & doors, 2 mm thick for gland plates, powder coated in approved shade,PVC colour coded with heat shrinkable coloured sleeves 800Amps TPN Aluminum alloy bus bar of high conductivity, DMC/ SMC bus bar supports, entire panel shall have a common copper earth bar of size 25mmx5mm at the rear with 2 Nos earth stud, solid sections from main bus bars to MCCB with required size of Al. bus bars and control wiring with 1.5 sqmm PVC insulated copper conductor S/C cable, cable alleys, cable gland plates in two half including connections, i/c providing following switch gears and providing necessary channel / angle iron supports of suitable size for mounting the panel,interconnections, testing,commissioning etc as required along with accessories, etc as required as p
Sector: Telecommunication