Description: SITC of VRV VRF System at Sector 19 Dwarka Name of Work Development of Sports Complex at Sector 19 Phase I Dwarka Sub Head SITC of VRV VRF System at Sector 19 Dwarka
Details: PART-I(Boxing, Yoga, Table Tennis, GYM, Shooting Range and Badminton Hall)Supply Installation ,Testing & Commissioning of modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling and heating having all hermetically sealed inverter type Scroll Compressor(s), minimum two compressors for above 14 HP modules, microprocessor based Controller, top discharge type condensing unit(s), with R 410 A Refrigerant, vibration isolators, with suitable foundation etc. complete as required. The unit shall deliver the rated capacity at AHRI Conditions and work even at 50°C ambient temperature without tripping. The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required. The COP at AHRI and 100% load conditions shall not be less than 3.6. IEER not less than 6.5The machine should deliver EER 3.43 / 5.34/ 6.97 @ 100% / 75% / 50% for All m
Sector: Urban Authority